The IDA8C-RU from Bogen is a third-generation modular system that complies with current architectural demands requiring IP and/or fiberoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
The IDA8C Controller unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, with front panel access for a fully monitored fireman’s microphone and emergency message trigger buttons. IDA8C also supports amplifier monitoring with hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up to four PSS-AS monitored microphone consoles and up to eight monitored amplifiers plus two backup amplifiers, paging into 8 different zones per unit with A/B line detection according to BS5939 part 8. Two card slots are provided for either 4-channel 0dB audio input or 4-channel audio cards. Optional AES/EBU cards are also available.
Features
- Public address and emergency sound system control unit
- Fully digital with 8 audio inputs and 8 audio outputs
- 4 dedicated and monitored PDC-ports for firemen’s microphones
- 2 dedicated audio in and outputs for back-up amplifiers
- Enhanced loudspeaker line surveillance for AB-zoned installation
- Simultaneous control and routing of 48 audio channels over dedicated network
- Equipped as standard with RJ45 network cards (NET-C1) for links up to 100 m
- Optional fiberoptic cards for links up to 20 km
- 9 supervised control inputs and 8 control outputs
- Ethernet interface for configuration, control, diagnostics and logging
- Digital storage for up to 4 hours of prerecorded messages
- 4 message players
- Stores the last 999 fault events
- EN54-16 certified