The PDD-FT transfers the input power from the normally ON output pair “-N/ON+” too the normally OFF output pair “-N/OFF+” when triggered. The unit is triggered when the supervised (EOL), end of line resistor is opened or shorted. The triggered form C user contacts indicate the state of the trigger. A typical application of the PDD-FT is to place a distribution board on one or both of the outputs, one of our power supplies on the Input, then connecting the EOL at a fire alarm panel to transfer the power from one distribution board to another when the Fire alarm panel is in the alarm condition. The transferred power would be used to unlock doors, shut down air systems, or return elevators to an exit floor.
Features
- Non Latching or Latching mode
- Universal 11-29VDC Operation
- Reverse polarity protected
- Normally ON & Normally OFF Output
- Output LED’s indicate condition
- Outputs can be Triggered with:
-N/O or N/C Switch with Supervised (EOL)
-N/C Switch with (OVR)over ride
-N/C Switch with AUX-IN auxiliary
-Ground on any trigger input when(GRN Jumper is enabled - Form C Contacts Indicates Trigger Status
- 12 Amp Transfer Relay Contacts
- UL Listed UL & ULC 1481, 294, 603 NFPA72, & CSFM