Altronix T1KE3F4 kit consists of Trove1 enclosure and TLU1 Altronix & Kisi backplane with 12VDC or 24VDC (factory set at 24VDC) @ 6A power supply/charger and four (4) fuse protected output access control module. This kit also accommodates one (1) Kisi Pro Controller for up to four (4) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Features
eFlow6NB Power Supply/Charger
Input
- Voltage: 120VAC, 60Hz, 3.5A max
- Fusing: 5A / 250V
Output
- Voltage: 24VDC
- Current: 6A continuous
- Other: Overvoltage protection. Filtered and regulated
Battery Backup
- Capacity: 7AH/12VDC (Up to 2 within enclosure) 40AH/65AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Fuse Rating: 10A @ 32V
- Failover: Upon AC loss, instantaneous
Fire Alarm Disconnect
- Supervised: Latching or non latching
- EOL: 10K Resistor
Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge
Indicators LED
- Input: 120VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
ACM4 Access Power Controller
Input
- Voltage: 24VDC from eFlow6NB
- Input Fuse: 10A / 32V
Outputs
- Voltage: 24VDC
- Four (4) independently controlled fused outputs:
- a) Four (4) Fail-Safe and/or Fail-Secure power outputs
- Form “C” Relays rated 28VAC or VDC @ 2.5A
- b) Auxiliary power outputs (unswitched)
- c) Any combination of the above
Outputs Ratings
- Fuses: 3A/32V
Indicators (LED’s)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
Temperature
- Operating: 0° C to 49° C (32° F to 120° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
Relative Humidity
- Relative Humidity 85% +/- 5%
BTU/Hr (approx.):
- 87 BTU/Hr



















Reviews