Altronix T2KE3316DV kit consists of Trove2 enclosure, TLU2 Kisi/Altronix backplane with two (2) 12 or 24VDC @ 6A power supply/chargers, and two eight (8) PTC protected output access control modules. This kit also accommodates up to four (4) Kisi Pro Controllers for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Features
Two (2) AL600XB220 Power Supply/Charger
- Input
- Voltage: 220VAC (range 198VAC-256VAC), 50/60Hz, 1.5A. max
- Input Fuse: 5A / 250V
- Outputs
- Voltage: 12VDC or 24VDC selectable
- Current: 6A @ 12VDC or 24VDC continuous max
- Other: Filtered and regulated
- Battery Backup (not included)
- Capacity: 7AH / 12VDC (Up to 4 within enclosure); 12AH / 12VDC (up to 4 within enclosure); 40 AH / 65 AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Failover: Upon AC loss, instantaneous
- Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
- Indicators LED
- Input: 220VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
Two (2) ACM8CB Access Power Controllers
- Input
- Voltage: 24VDC from AL600XB220
- Input Fuse: 10A / 250V
- Outputs
- Voltage: 24VDC
- Eight (8) 24VDC independently controlled PTC outputs:
a) Fail-Safe and/or Fail-Secure power outputs Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above - Outputs Ratings
- PTCs: 2.5A.
- Indicators (LED’s)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
- Temperature
- Operating: 0° C to 49° C (32° F to 120° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
- Relative Humidity
- Relative Humidity 85% +/- 5%
- BTU/Hr (approx.):
- 12VDC: 74 BTU/Hr
- 24VDC: 148 BTU/Hr
- 12VDC and 24VDC: 111 BTU/Hr