Altronix T2KSK7F12 kit consists of Trove2 enclosure, TKS2 Keri Systems/Altronix backplane with one (1) 24VDC @ 10A power supply/charger, one (1) dual output fused access power controller, one (1) voltage regulator, one (1) dual input fused power distribution module, and one (1) fused access power controller.This kit also accommodate various combinations of Keri Systems boards for up to twelve (12) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Features
AL1024ULXB2 Power Supply/Charger
Input
- Voltage: 115VAC 60Hz, 4.2A max
- Main Fuse: 5A / 250V
Outputs
- Voltage: 24VDC
- Current: 10A @ 24VDC continuous max
- Other: Overvoltage protection. Filtered and regulated
Battery Backup
- Capacity: 12AH /12VDC (2 within enclosure), 40 AH / 65 AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Failover: Upon AC loss, instantaneous
Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
Indicators LED
- Input: 115VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
ACM4 Access Power Controller
Input
- Voltage: 24VDC from AL1024ULXB2
- Input Fuse: 10A / 32V
Outputs
- Voltage: 24VDC
- Four (4) independently controlled 2.5A outputs:
- a) Four (4) Fail-Safe and/or Fail-Secure power outputs
- b) Four (4) dry form “C” 5A rated relay outputs
- c) Any combination of the above
- Four (4) auxiliary power outputs (unswitched)
Outputs Ratings
- Fuses: 3A / 32V
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
VR6 Voltage Regulator
Input
- Voltage: 24VDC from AL1024ULXB2
Output
- Voltage: 12VDC
- Current: 6A continuous
- Other: Surge suppression
Indicators LED
- Input: 24VDC is present
- Output: Powered
ACMS8 Dual Input Access Power Controller
Input
- Voltage: 24VDC from AL1024ULXB2 and 12VDC from VR6
- Input Fuse: 15A / 32V
Outputs
- Voltage: 12 or 24VDC individually selectable
- Eight (8) selectable 12VDC – 24VDC independently controlled outputs or eight (8) indepently controlled Form “C” relay outputs:
- a) Fail-Safe and/or Fail-Secure power outputs
- b) Form “C” Relays rated 28VAC or VDC @ 2.5A Rated
- c) Auxiliary power outputs (unswitched)
- d) Any combination of the above
- Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2
- Individual outputs may be set to OFF position for servicing
Outputs Ratings
- Fuses: 3A/32V
Indicators (LED’s)
- Red LEDs: Outputs are triggered (relays energized)
- Blue LED: FACP disconnect is triggered
Individual voltage LEDs:
- Green: 12VDC
- Red: 24VDC
PDS8 Dual Input Power Distribution Module
Input
- Voltage: 24VDC from AL1024ULXB2 and 12VDC from VR6
- Input Fuse: 10A / 32V
Outputs
- Voltage: 12VDC or 24VDC individually selectable
- Output Fuses: 3A/32V
Indicators (LED)
- DC Output: Eight (8) individual output LEDs
- Green: 12VDC
- Red: 24VDC
Environmental
Temperature
- Operating: 0° C to 50° C (32° F to 122° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
Relative Humidity
- Relative Humidity 85% +/- 5%
BTU/Hr (approx.):
- 131 BTU/Hr



















Reviews