Altronix T2MK38 kit consists of Trove2 enclosure and TM2 Altronix & Mercury backplane with 12VDC or 24VDC (factory set at 24VDC) @ 6A power supply/charger, 12VDC voltage regulator, eight (8) fuse protected output dual voltage power distribution module and eight (8) fuse protected output access control module. This kit also accommodates various combinations of Mercury* boards for up to eight (8) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
*Also compatible with these authentic Mercury partners: AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, Lenel/S2, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic Video Insight, Quintron, RS2, Schneider Electric, Vanderbilt.
Features
AL600ULXB Power Supply/Charger
- Input
- Voltage: 115VAC, 60Hz, 3.5A max
- Fusing: 5A / 250V
- Output
- Voltage: 12VDC or 24VDC selectable
- Current: 6A @ 12VDC or 24VDC continuous max
- Other: Overvoltage protection. Filtered and regulated
- Battery Backup (not included)
- Capacity: 7AH / 12VDC (up to 2 within enclosure); 40 AH / 65 AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Failover: Upon AC loss, instantaneous
- Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
- Indicators LED
- Input: 115VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
PDS8 Dual Input Power Distribution Module
- Input
- Voltage: 12VDC from VR6 and 24VDC from AL600ULXB
- Input Fuse: 10A / 32V
- Outputs
- Voltage: 12VDC and/or 24VDC
- Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2
- Individual outputs may be set to OFF position for servicing
- Outputs Ratings
- Fuses: 3A / 32V
- Indicators LED
- DC Output: Eight (8) individual output LEDs
- Green: 12VDC
- Red: 24VDC
VR6 Voltage Regulator
- Input
- Voltage: 24VDC from AL600ULXB
- Output
- Voltage: 12VDC
- Current: 6A continuous
- Other: Surge suppression
- Indicators LED
- Input: 24VDC is present
- Output Powered
ACM8 Access Power Controller
- Input
- Voltage: 24VDC from AL600ULXB
- Input Fuse: 10A / 250V
- Outputs
- Voltage: 24VDC
- Eight (8) 24VDC independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above - Output Fuses: 3.5A/250V
- Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
- Temperature
- Operating: 0° C to 49° C (32° F to 120° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
- Relative Humidity
- Relative Humidity 85% +/- 5%
- BTU/Hr (approx.):
- 87 BTU/Hr



















Reviews