Altronix T2PHK77F24 kit consists of Trove2 enclosure, TCV2 Openpath/Altronix backplane with two (2) 24VDC @ 10A power supply/chargers, and three (3) eight (8) fuse protected output access control modules. This kit also accommodates up to one (1) Openpath Core, two (2) Elevator Board, three (3) 4-Port or 8-Port modules for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Features
Two (2) eFlow104NB Power Supply/Chargers
Input
- Voltage: 120VAC, 60Hz, 9A max
- Input Fuse: 6.3A / 250V
Output
- Voltage: 24VDC 10A
- Auxiliary: 1A (unswitched)
- Protection: Overvoltage protection. Filtered and regulated
Battery Backup
- Type: Sealed lead acid or gel type
- Fuse Rating: 15A @ 32VDC
- Failover: Upon AC loss, instantaneous
Fire Alarm Disconnect
- Supervised: Latching or non latching
- EOL: 10K Resistor
Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge
Indicators LED
- AC Input: 120VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
Three (3) ACM8 Access Power Controllers
Input
- Voltage: 24VDC from eFlow104NB
- Input Fuse: 10A / 250V
Outputs
- Voltage: 24VDC
- Eight (8) 24VDC independently controlled fused outputs:
- a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A
- b) Auxiliary power outputs (unswitched)
- c) Any combination of the above
- Output Fuses: 3.5A/250V
Indicators (LED’s)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
Temperature
- Operating: 0° C to 49° C (32° F to 120° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
Relative Humidity
- Relative Humidity 85% +/- 5%
BTU/Hr (approx.):
- 24VDC: 290 BTU/Hr
- 12VDC and 24VDC: 111 BTU/Hr



















Reviews