Altronix T2SAK7512 kit consists of Trove2 enclosure, TSA2 Salto/Altronix backplane with one (1) 24VDC @ 10A and one (1) 12VDC @ 10A power supply/chargers, one (1) 8-output fused access power controllers, one (1) 4-output fused access power controller and one (1) 8-output dual output fused power distribution module.
This kit also accommodates up to six (6) Salto CU42E0, CU4200 or CU4EB8 modules for up to twelve (12) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Features
AL1024ULXB2 Power Supply/Charger – 1
- Input
- Voltage: 115VAC, 60Hz, 4.2A max
- Main Fuse: 5A / 250V
- Output
- Voltage: 24VDC
- Current: 10A @ 24VDC continuous max
- Other: Overvoltage protection. Filtered and regulated
AL1012ULXB Power Supply/Charger – 2
- Input
- Voltage: 115VAC, 60Hz, 2.6A max
- Main Fuse: 5A / 250V
- Output
- Voltage: 12VDC
- Current: 10A @ 12VDC continuous max
- Other: Overvoltage protection. Filtered and regulated
- Both Power Supplies
- Battery Backup (not included)
- Capacity: 7AH /12VDC (4 within enclosure); 40 AH / 65 AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Failover: Upon AC loss, instantaneous
- Supervision
- AC Failure: Form “C” contacts
- Battery: Form “C” contacts
- Indicators LED
- Input: 115VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
PDS8 Dual Input Power Distribution Module
- Input
- Voltage Range: 24VDC from AL1024ULXB2 and 12VDC from AL1012ULXB
- Main Fuse: 10A/32V
- Outputs
- Voltage: 12 or 24VDC individually selectable
- Output Fuses: 3A/32VDC
- Indicators (LED)
- DC Output: Eight (8) individual output LEDs
- Green: 12VDC
- Red: 24VDC
ACM8 Access Power Controller
- Input
- Voltage: 24VDC from AL1024ULXB2
- Main Fuse: 10A / 250V
- Outputs
- Voltage: 24VDC
- Eight (8) 24VDC independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above - Output Fuses: 3.5A / 250VDC
- Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
ACM4 Access Power Controller
- Input
- Voltage: 24VDC from AL1024ULXB2
- Main Fuse: 10A / 32V
- Outputs
- Voltage: 24VDC
- Four (4) independently controlled 2.5A outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs.
c) Any combination of the above - Output Fuses: 3A / 32V
- Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
- Temperature
- Operating: 0° C to 50° C (32° F to 122° F)
- Storage: – 20° C to 70° C ( – 4° F to 158° F)
- Relative Humidity
- Relative Humidity 85% +/- 5%
- BTU/Hr (approx.):
- 177 BTU/Hr



















Reviews
There are no reviews yet.